Asia Unique LED Lighting Co., Ltd.
Home  >  Products  >  Solutions  >  Emergency Lighting

Products

Solutions

>
<

CLASSIC AU02 Batten-Emergency


AU02 Maintained Emergency LED Batten(图1)


● Wire from back or two ends,with big entry hole;

● Big Terminal Block or Quick play & plug connector, easy installation

● LED Replaceable board, very even light distribution

● Suspension strap attached to the lamp & base part, makes installation easier

● Can be Surface Mounted or Suspended

● Can be linked one to another, end by end, without gap

● CE, Rohs, SAA, C-tick & AS/NZ 2293.3 Approved

● LiFePO4 Battery adopted, 3.5W run 3 hours

● 3 years warranty for whole lamp


Applications:

  ● Warehouses● Supermarkets● Shopping Malls
  ● Office Buildings ● Workshops● Car Parks


Specification Video Contact

Product Dimention

AU02 Maintained Emergency LED Batten(图2)


Technical Specifications

AU02 Maintained Emergency LED Batten(图3)


Packing information

AU02 Maintained Emergency LED Batten(图4)


Wiring Diagream

AU02 Maintained Emergency LED Batten(图5)



Testing

When luminaire is permanently connected to mains supply, allow the luminaire to fully charge for 24 hours.

Conduct following tests once the battery has fully charged:


Test 1:

A commissioning discharge test must be carried out once the luminaire is connected to mains supply.

The emergency luminaire must remain illuminated for at least 2 hours after disconnection from the mains power.

NOTE: The luminaire works on standard power when connected to mains supply and switches to 3.5W power during.

emergency mode operation.


Test 2:

Subsequent tests, performed every 6 months, require the luminaire to successfully operate in emergency mode for 90mins.

NOTE: A record shall be maintained of all the discharge tests performed on site at all times.



Test Switch and LED Indicator:

The Test Switch and LED indicator on the luminaire provide an indication of the status of the luminaire during testing and normal operation

AU02 Maintained Emergency LED Batten(图6)

NOTE: * Self-test option is available

           * It is recommended to disconnect the battery before storage or delievery

           * Battery should be charged once in six months in order to keep it in initial performance



Install Instruction


AU02 Maintained Emergency LED Batten(图7)

AU02 Maintained Emergency LED Batten(图8)


Please Note:

* Turn off and isolate the electrical supply before connecting this fitting to the building wires.

* Must be installed, or connected by licenced electrician.

* The Luminaires are intended for indoor use only. 


X

Leave a Message
we will get back to you ASAP !